Features and Advantages
High Reliability:
• Wide input voltage range +/- 20% (up to -40% at reduced load)
• Hot-swappable function ensures uninterrupted operations during maintenance
• Dual system control card prevents single failure point
• Intelligent fan control and redundant design for energy saving: 25% load can be driven when 2 fans
fail and 50% load when 1 fan fails
• Parallel expansion up to four systems without requiring additional hardware
High Performance:
• High efficiency in online mode (>96%) reduces heat dissipation and limits power consumption costs
• THDi≤3% and input power factor 0.99 reduce the pollution to grid and reduce upstream investment costs
• Full rated power (kVA=kW) to maximize power availability
• Efficiency>99% in ECO mode gives significant cost reduction
• Advanced power module sleep mode, prolong the service life of power module
• Allow 100% three phase unbalance load
• Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
• Loop test function without load enables on-site commission
• Small footprint, 300kW only covers 0.5m2
TECNED X-PND Specifications
MODEL | X-Pnd 120 | X-Pnd 200 | X-Pnd 300 | X-Pnd 400 | X-Pnd 500 | X-Pnd 600 |
Power Module | XPD – 30 | XPD – 50 | ||||
Input | ||||||
Rated Voltage (Vac) | 380/400/415 | |||||
Voltage Range (Vac) | L:L 138~485 | |||||
Input Wiring | 3Ph+N+PE | |||||
Input Frequency (Hz) | 40-70 | |||||
Bypass Voltage Range (Vac) | -15% (-20%/-30% optional) ~+15%(+10% /+20% optional) | |||||
Power Factor | ≥0.99 | |||||
THDi | <5% (nolinear, full load) | |||||
Phase | 3Φ4W+PE | |||||
Battery (Vdc) | ±192 (±180 ~ ±276 settable) | ±240 (±180 ~ ±276 settable) | ||||
Charging Current (A) | N× 10 Maximum (N = the number of power module) | |||||
Output | ||||||
Capacity (kVA) | 120 | 200 | 300 | 400 | 500 | 600 |
Power Factor | 1 | |||||
Power Factor | 3Φ4W+PE | |||||
Waveform | sine wave | |||||
Voltage (Vac) | L-L:380,400,415 ±1% | |||||
Frequency (Hz) | 50/60± 0.2% (battery mode) | |||||
Three Phase Difference | ≤1 º | |||||
THDv | ≤1% (linear load, full load); | |||||
≤4% (nolinear load, full load) | ||||||
Static Bypass Transfer Time | 0 | |||||
System Efficiency | 96% | |||||
Parallel Mode | Advanced no-master-slave parallel technology, N+1 redundancy | |||||
Overload Capacity | 106-110% load for 60 minutes, 111%-130% load for 10 minutes, | |||||
131%-150% load for 1minute, 151%~200% load for 200ms. | ||||||
Others | ||||||
Approvals | CE (EN62040-2, IEC62040-1) | |||||
Operating Temperature (ºC) | 0~40 | |||||
Storage Temperature (ºC) | -40~70 | |||||
Relative Humidity | 0~95%, no condensation | |||||
Communication Function | RS485, RS232, dry contact (SNMP optional) | |||||
Noise (dB) | <65 | <70 | ||||
Power Module (kVA) | 30 | 50 | ||||
Power Module Dimension (W×D×H)(mm) | 500×700×130 | |||||
Weight (kg) | ||||||
Cabinet | 162 | 224 | 236 | 427 | ||
Bypass Module | 20 | 23 | 27 | 27 | 31 | 31 |
Power Module | 24 | 33 |