Online UPS 10-15-20-30-40kVA
• Programmable Input and output configuration 11/31/33
• High AC/AC Efficiency up to 95%
• Designed with ECO conservation mode
• Supports 4 Units Parallel
• Common battery parallel operation
• Programmable DC bus voltage
• Dry contacts with RS-485 (Modbus)
• SNMP with preloaded web interface (option)

Features and Advantages

High Reliability:

• Wide input voltage range +/- 20% (up to -40% at reduced load)
• Hot-swappable function ensures uninterrupted operations during maintenance
• Dual system control card prevents single failure point
• Intelligent fan control and redundant design for energy saving: 25% load can be driven when 2 fans
fail and 50% load when 1 fan fails
• Parallel expansion up to four systems without requiring additional hardware

High Performance:

• High efficiency in online mode (>96%) reduces heat dissipation and limits power consumption costs
• THDi≤3% and input power factor 0.99 reduce the pollution to grid and reduce upstream investment costs
• Full rated power (kVA=kW) to maximize power availability
• Efficiency>99% in ECO mode gives significant cost reduction
• Advanced power module sleep mode, prolong the service life of power module
• Allow 100% three phase unbalance load
• Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
• Loop test function without load enables on-site commission
• Small footprint, 300kW only covers 0.5m2

Tecned Flex UPS Specifications

TECNED UPS MODEL FLEX 10 FLEX 15 FLEX 20 FLEX 30 FLEX 40
Input
Voltage (Vac) 150-280 (L-N) or 260-485 (L-L)
Frequency (Hz) 40-70
Power Factor ≥ 0.99
THDi < 5%
Output
Capacity (kVA) 10 15 20 30 40
AC/AC Efficiency Up to 95%
Power Factor Up to PF 1
Voltage (Vac) 220/230/240 (L-N) 380/400/415 ± 1% (L-L), programmable
Frequency (Hz) 50/60 ± 0.1% (on battery)
THDv THD <2% (linear load),
THD <3% (nonlinear load)
Transfer Time (ms) 0
Overload 125% for 10 min, 150% for 1 min
ECOMode Yes
Battery
Voltage (Vdc) ± 120 – 280Vdc programmable / 25% derating < 158Vdc
Charging Current (A) 4 (1-10A programmable) 8 (1-20A programmable)
12V VRL /1.2V Nicd ± 12-20 block / ± 120-170 cells
Communication Interface RS485 MODBUS + EPO + dry contact standard
TCP – IP / SNMP / RS232 option
Input / Output configuration 11 / 31 / 33 31 / 33
Display Blue screen LCD
Alarm Low battery, Abnormal AC input, UPS failure
Protection Low battery, overload, short – circuit and over temperature, etc.
Noise (dB) < 55
Working Temperature (°C) -5 ~ 40
Relative Humidity ± 0 ~ 95%, No condensation
Dimension (W×D×H)(mm) 1125 x 510 x 600 1450 x 510 x 790
Weight with (w/o) battery (kg) 175 (90) 200 (90) 200 (90) 330 (90) 435 (90)
International standards IEC 62040-1, YD – T 1095-2018, GB / T 14715-2017