• All Hot-swappable Design
• Power Factor 1 (kVA=kW)
• High Efficiency 96%
• System Parallel
• Fault Trace Management

Features and Advantages

High Reliability:

• Wide input voltage range +/- 20% (up to -40% at reduced load)
• Hot-swappable function ensures uninterrupted operations during maintenance
• Dual system control card prevents single failure point
• Intelligent fan control and redundant design for energy saving: 25% load can be driven when 2 fans
fail and 50% load when 1 fan fails
• Parallel expansion up to four systems without requiring additional hardware

High Performance:

• High efficiency in online mode (>96%) reduces heat dissipation and limits power consumption costs
• THDi≤3% and input power factor 0.99 reduce the pollution to grid and reduce upstream investment costs
• Full rated power (kVA=kW) to maximize power availability
• Efficiency>99% in ECO mode gives significant cost reduction
• Advanced power module sleep mode, prolong the service life of power module
• Allow 100% three phase unbalance load
• Frequency converter function(60Hz to 50Hz or 50Hz to 60Hz)
• Loop test function without load enables on-site commission
• Small footprint, 300kW only covers 0.5m2

2021-image-product-x-pnd

TECNED X-PND Specifications

MODEL X-Pnd 120 X-Pnd 200 X-Pnd 300 X-Pnd 400 X-Pnd 500 X-Pnd 600
Power Module XPD – 30 XPD – 50
Input
Rated Voltage (Vac) 380/400/415
Voltage Range (Vac) L:L 138~485
Input Wiring 3Ph+N+PE
Input Frequency (Hz) 40-70
Bypass Voltage Range (Vac) -15% (-20%/-30% optional) ~+15%(+10% /+20% optional)
Power Factor ≥0.99
THDi <5% (nolinear, full load)
Phase 3Φ4W+PE
Battery (Vdc) ±192 (±180 ~ ±276 settable) ±240 (±180 ~ ±276 settable)
Charging Current (A) N× 10 Maximum (N = the number of power module)
Output
Capacity (kVA) 120 200 300 400 500 600
Power Factor 1
Power Factor 3Φ4W+PE
Waveform sine wave
Voltage (Vac) L-L:380,400,415 ±1%
Frequency (Hz) 50/60± 0.2% (battery mode)
Three Phase Difference ≤1 º
THDv ≤1% (linear load, full load);
≤4% (nolinear load, full load)
Static Bypass Transfer Time 0
System Efficiency 96%
Parallel Mode Advanced no-master-slave parallel technology, N+1 redundancy
Overload Capacity 106-110% load for 60 minutes, 111%-130% load for 10 minutes,
131%-150% load for 1minute, 151%~200% load for 200ms.
Others
Approvals CE (EN62040-2, IEC62040-1)
Operating Temperature (ºC) 0~40
Storage Temperature (ºC) -40~70
Relative Humidity 0~95%, no condensation
Communication Function RS485, RS232, dry contact (SNMP optional)
Noise (dB) <65 <70
Power Module (kVA) 30 50
Power Module Dimension (W×D×H)(mm) 500×700×130
Weight (kg)
Cabinet 162 224 236 427
Bypass Module 20 23 27 27 31 31
Power Module 24 33

Copyright 2023 @ Tecned.com

Tjalke de Boerstrjitte 12

8561 EL, Balk
The Netherlands
+31-514-820222

Enquiries: [email protected]