ONV (19inch) product range

Industrial grade 19inch based UPS

TECNED Industrial grade UPS are based on transformer technology for robustness and endurance. The input and output isolation transformers protect the semiconductors against spikes, surges, peak currents and distortion, supply short circuit currents and filtering noise. Transformer based technologies offer therefore a longer service life and higher degree of protection.

Based on this topology, TECNED provides a highly reliable charger / inverter product combination designed for demanding operating environments.

The ONV(19inch) series strictly adheres to a truly industrial design and is built for 20 years operational life-time.

Tecned ONV (19inch) Specifications

1 – INPUT
nominal input voltage [V] 1 Phase 110 / 220 / 230 / 240 Vac
input voltage range [V] +/- 20%
input frequency range [Hz] 40Hz to 70Hz
input current THD [%] <10
power factor PF 0.98 + soft start
overall efficiency [%] Up to 95% (depending on DC bus voltage)
galvanic isolation Yes (input isolation transformer)
2 – DC BUS / BATTERY
nominal DC busvoltage [Vdc] 24, 48, 60, 110 (125), 220 (240) Vdc
DC voltage range [Vdc] 24 – 280Vdc
battery charging characteristic IU (DIN 41773), T° compensated float voltage
float charge setting (Cell) [Vdc] 1.40-1.42V for Ni-cd or 2.17 -2.27V for Lead acid
output current I-nominal [A] Up to 100A (depending on DC voltage level)
battery charge current limit [A] from 0 to max current / dip-switch setting
output voltage regulation [%] < 1% ( 0.5% static)
load step response time [ms] <2% ( Charge current 0.2C)
current limiting [%] Yes
current accuracy [%] 2%
long-term stability [%] 0.15% for 1000 Hrs
3 – OUTPUT
nominal output voltage [V] 1 Phase 110 / 220 / 230 / 240 Vac
nominal output rating [kVA] 1 to 10 kVA (up to 2,2kVA in a single module)
output powerfactor [PF] 0.9
output frequency 50 / 60 Hz, +/- 0.1% free running
output waveform [F] SineWave
output voltage TH-V [%] Max 1,5%@ 100% liniar load
output voltage TH-V [%] Max 3% @ non-linear load
output voltage stability [%] Static +/- 1%
output voltage stability [%] Dynamic +/- 3%, 100% load step
recovery time [ms] < 20 msec
overall efficiency [%] Up to 95% (depending on DC bus voltage)
crest Factor > 3:1
galvanic isolation Yes (Inverter Output Transformer)
4 – STATIC TRANSFER SWITCH (OPTION)
single / leg static switch build-in with automatic output sensing *
transfer alternative module dip-switch setting on-board *
double leg static switch build-in with separate bypass input
preferred source select dip-switch setting on-board
* Requires RJ45 plug connection between modules
5 – BASIC USER INTERFACE
LED Operation (green) LED Rectifier Fault (RED)
LED General alarm (red) LED Inverter Fault (RED)
LED Utility Failure (red) button on
LED DC voltage low (red) button off
LED Battery Operation (Yellow) button buzzer off
LED Fan failure alarm (red) button lamp test
6 – ENCLOSURE
base / cover AluZinc 2mm / AluZinc 1,2mm
dims (hxd) 7U high / 700mm deep
weight 25-110 Kg depending on configuration
fans Speed controlled / front access for replacement
cable entry back, terminal connection
external contacts 2x potential free contact (General Alarm / Fan Failure)
protection IP 20
7 – STANDARDS
ISO 9001 quality management systems
IEC 60146 semiconductor converters – general requirements and line commutated converters
EMC 55011 industrial, scientific, and medical (ISM) radio-frequency equipment—radio disturbance characteristics—limits and methods of measurement; amendment A1:1999 to EN 55011:1998.
IEC 62040-1 uninterruptible power systems (UPS) Part 1: general and safety requirements for UPS
IEC 61000-3-12 electromagnetic compatibility (EMC) – Part 3-12: Limits – limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A
IEC 61000-6-5 low voltage AC surge 1.2/50 μs, 2kV line to ground, 1kV line to line (equipment installed in power stations and MV substations. low voltage DC surge 1.2/50 μs, 2kV line to ground, 1kV line to line
8 – ENVIRONMENT
storage temperature -25 to + 70 °C
operating temperature -10 to + 40 °C
humidity max. 95%
installation altitude up to 1000 meter without derating
audible noise 55 dBA
cooling forced air (2x fan)
9 – TECHNOLOGY
IGBT conversion technology with build-in galvanic separation transformer high reliable due to failsafe control system and protection circuits optional build-in STS for active transition mode or bypass operation