ONV (19inch) product range
Industrial grade 19inch based UPS
TECNED Industrial grade UPS are based on transformer technology for robustness and endurance. The input and output isolation transformers protect the semiconductors against spikes, surges, peak currents and distortion, supply short circuit currents and filtering noise. Transformer based technologies offer therefore a longer service life and higher degree of protection.
Based on this topology, TECNED provides a highly reliable charger / inverter product combination designed for demanding operating environments.
The ONV(19inch) series strictly adheres to a truly industrial design and is built for 20 years operational life-time.
Tecned ONV (19inch) Specifications
1 – INPUT | ||
nominal input voltage | [V] | 1 Phase 110 / 220 / 230 / 240 Vac |
input voltage range | [V] | +/- 20% |
input frequency range | [Hz] | 40Hz to 70Hz |
input current THD | [%] | <10 |
power factor | PF | 0.98 + soft start |
overall efficiency | [%] | Up to 95% (depending on DC bus voltage) |
galvanic isolation | Yes (input isolation transformer) | |
2 – DC BUS / BATTERY | ||
nominal DC busvoltage | [Vdc] | 24, 48, 60, 110 (125), 220 (240) Vdc |
DC voltage range | [Vdc] | 24 – 280Vdc |
battery charging characteristic | IU (DIN 41773), T° compensated float voltage | |
float charge setting (Cell) | [Vdc] | 1.40-1.42V for Ni-cd or 2.17 -2.27V for Lead acid |
output current I-nominal | [A] | Up to 100A (depending on DC voltage level) |
battery charge current limit | [A] | from 0 to max current / dip-switch setting |
output voltage regulation | [%] | < 1% ( 0.5% static) |
load step response time | [ms] | <2% ( Charge current 0.2C) |
current limiting | [%] | Yes |
current accuracy | [%] | 2% |
long-term stability | [%] | 0.15% for 1000 Hrs |
3 – OUTPUT | ||
nominal output voltage | [V] | 1 Phase 110 / 220 / 230 / 240 Vac |
nominal output rating | [kVA] | 1 to 10 kVA (up to 2,2kVA in a single module) |
output powerfactor | [PF] | 0.9 |
output frequency | 50 / 60 Hz, +/- 0.1% free running | |
output waveform | [F] | SineWave |
output voltage TH-V | [%] | Max 1,5%@ 100% liniar load |
output voltage TH-V | [%] | Max 3% @ non-linear load |
output voltage stability | [%] | Static +/- 1% |
output voltage stability | [%] | Dynamic +/- 3%, 100% load step |
recovery time | [ms] | < 20 msec |
overall efficiency | [%] | Up to 95% (depending on DC bus voltage) |
crest Factor | > 3:1 | |
galvanic isolation | Yes (Inverter Output Transformer) | |
4 – STATIC TRANSFER SWITCH (OPTION) | ||
single / leg static switch | build-in with automatic output sensing * | |
transfer alternative module | dip-switch setting on-board * | |
double leg static switch | build-in with separate bypass input | |
preferred source select | dip-switch setting on-board | |
* Requires RJ45 plug connection between modules | ||
5 – BASIC USER INTERFACE | ||
LED Operation (green) | LED Rectifier Fault (RED) | |
LED General alarm (red) | LED Inverter Fault (RED) | |
LED Utility Failure (red) | button on | |
LED DC voltage low (red) | button off | |
LED Battery Operation (Yellow) | button buzzer off | |
LED Fan failure alarm (red) | button lamp test | |
6 – ENCLOSURE | ||
base / cover | AluZinc 2mm / AluZinc 1,2mm | |
dims (hxd) | 7U high / 700mm deep | |
weight | 25-110 Kg depending on configuration | |
fans | Speed controlled / front access for replacement | |
cable entry | back, terminal connection | |
external contacts | 2x potential free contact (General Alarm / Fan Failure) | |
protection | IP 20 | |
7 – STANDARDS | ||
ISO 9001 | quality management systems | |
IEC 60146 | semiconductor converters – general requirements and line commutated converters | |
EMC 55011 | industrial, scientific, and medical (ISM) radio-frequency equipment—radio disturbance characteristics—limits and methods of measurement; amendment A1:1999 to EN 55011:1998. | |
IEC 62040-1 | uninterruptible power systems (UPS) Part 1: general and safety requirements for UPS | |
IEC 61000-3-12 | electromagnetic compatibility (EMC) – Part 3-12: Limits – limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A | |
IEC 61000-6-5 | low voltage AC surge 1.2/50 μs, 2kV line to ground, 1kV line to line (equipment installed in power stations and MV substations. low voltage DC surge 1.2/50 μs, 2kV line to ground, 1kV line to line | |
8 – ENVIRONMENT | ||
storage temperature | -25 to + 70 °C | |
operating temperature | -10 to + 40 °C | |
humidity | max. 95% | |
installation altitude | up to 1000 meter without derating | |
audible noise 55 dBA | ||
cooling | forced air (2x fan) | |
9 – TECHNOLOGY | ||
IGBT conversion technology with build-in galvanic separation transformer high reliable due to failsafe control system and protection circuits optional build-in STS for active transition mode or bypass operation |