ONV ( SF/D ) product range

“The TECNED ONV(SF/D) UPS series is available with single phase and three phase input and single phase output with ratings up to 100 kVA in a single enclosure. The ONV (SF/D) series can be configured to charge common battery types from VRLA to NICAD.

The ONV (SF/D) series can be supplied as standard or fault tolerant systems within a single enclosure to meet customer requirements for safety and reliability.

The ONV-SF (software free) model is a strictly analog UPS available with natural convection and forced air cooling depending on rating. Standard features include output V/A metering, mains failure / DC-high/low and general alarm with potential free contacts and input/output and battery fuse monitoring.

The ONV-D model includes an additional digital controller with LCD display that shows the systems current state of operation and system values, allows setting of system parameters and includes event and alarm logs.

Option list ONV (SF/D)

  • Extend to 12x PFC (NO/NC) with LED.
  • Fan failure alarm.
  • Manual / automatic boost charge.
  • Individual fuse failure indicator.
  • DC ground fault.
  • Over temperature.
  • Up to 6 (DIN 96) meters / cabinet
  • Manual bypass switch

Additional options ONV (SF/D)

  • Advanced Battery Monitoring.
  • Battery asymmetric supervision.
  • Programmable values for charge voltage/current, boost-charge.
  • Single or double leg static bypass
  • RS485 / Modbus communication.

Tecned ONV (SF/D) Specifications

Input Voltage single phase 110/120/200/220/230/240/277V, (2W+E)
Voltage three phase 208/220/240/380/415/480V, (3W+E)
Voltage tolerance + 15% / – 20% (-20% start battery operation)
Frequency 50Hz / 60Hz +/- 10%
Harmonic distortion < 5% THDI
Power Factor 0.99
Battery Voltage (nominal) 24 / 48 / 110 (125) / 220 Vdc
Characteristic I-U according to DIN 41773
Output Voltage 110/120/200/220/230/240/277V+N
Static stability +/- 1%
Voltage THD Max 1.5% for 100% linear load
Frequency 50Hz / 60Hz (selectable) +/- 0.1% (free running)
Power factor 0.9 PF Lag
General Ambient temperature -20 to +70 °C storage / -10 to +40 °C operation
Altitude above sea level 1000 m
Enclosure Aluzinc frame / powder coat RAL 7035
Standards Safety IEC/EN 62040-1 / EMC 55011
Conformity IEC 60146 / CE-Label